A transformer operating at primary voltage $8\ \mathrm{kV}$ and secondary voltage $160\ \mathrm{V}$ serves a load of $80\ \mathrm{kW}$. Assuming the transformer to be ideal with purely resistive load and working on unity power factor, the loads in the primary and secondary circuit would be
- (1)
$800\ \Omega$ and $1.06\ \Omega$
- (2)
$10\ \Omega$ and $500\ \Omega$
- (3)
$800\ \Omega$ and $0.32\ \Omega$
- (4)
$1.06\ \Omega$ and $500\ \Omega$
Show answer
Option (3) is correct.
Key from source paper